● PMC96S meter is a multi-functional power monitoring meter, it combines function of collecting data and control, and it can replace many kind of meters, relays, transformers and others components.
● PMC96S can be installed in different positions of electricity distribution system.
● PMC96S is designed with RS-485 communication interface, which enable itself to be integrated into a variety of power monitoring systems. Data acquisition and remote control can be easily performed through the supporting management software or other industrial configuration software.Product Overview
Application scenarios
Industrial distribution automation system
Energy efficiency management system
Substation automation system
Electrical engineering of intelligent building
Power plant auxiliary power system
High and low voltage switchgear
Electrical Characteristics | ||
Measure type | 3P3W AC system | |
3P4W AC system | ||
Samping rate | 128 points per cycle | |
Data refresh rate | 1S | |
Measure accuracy | Cureen | ±0.2%FS |
Voltage | ±0.2%FS | |
Power | 0.5S | |
Frequency | ±0.001Hz | |
Active Energy | 0.5S | |
Reactive Energy | 1.0S | |
DC input(AI) | 0.5% FS | |
DC output(AO) | 0.5% FS | |
Input voltage characteristics | Measure Voltage | 3 *220/380V(Directly input) |
3 * 57.7/100V(PT secondary side) | ||
Allowed overload capability | 1.2times / continuous | |
Input resistance | 300KΩ/phase | |
Input current characteristics | Measure current | 5A (CT Secondary side)Or 1A (CT Secondaryside) |
Allowed overload capability | 1.2 times/continuous | |
Input resistance | <0.1Ω | |
Binary input | Working voltage | 15 VDC |
Input resistance | 12KΩ | |
Isolation voltage | 2KV | |
Relay Output | Node type | Mechanical contact |
Node capability | 220 VAC/5A、30 VDC/5A | |
4-20mA DC input measurement | Measure current | 4-20mA |
Allowed overload capability | 1.2 times / continuous | |
Input resistance | 10Ω | |
Isolation voltage | 2KV | |
0-5V DC input measurement | Measure Voltage | 0-5V |
Allowed overload capability | 1.2times / continuous | |
Input resistance | 12.5KΩ | |
Isolation voltage | 2KV | |
4-20mA DC output | Open-circuit Voltage | 15VDC |
Load capability | ≤600Ω | |
Isolation voltage | 2KV | |
Power supply | AC | 85~264 VAC/45-65Hz |
DC | 100~375 VDC | |
Power consumption | < 3W | |
Mechanical performance | ||
Weight | 0.5kg | |
IP Protection Level | Meter Panel IP52,Meter Host IP30 | |
Dimension | Host | 96 X 96 X 72 mm |
Host+modules | 96 X 96 X 120 mm | |
Working temperature | Display screen | -20~70℃ |
Meter | -25~70℃ | |
Storage temperature | Meter+display screen | -40~85℃ |
Relative humidity | 5% - 90%RH, No condensation | |
EMC | ||
Antistatic discharge interference | IEC 61000-4-2, Level 4 | |
Anti-fast transient group pulse | IEC 61000-4-4, Level 4 | |
Anti-surge | IEC 61000-4-5, Level 3 | |
Resistance to power frequency magnetic field | IEC 61000-4-8, Level 3 | |
Electrical insulation performance | ||
Insulation resistance | GB/T13729, >50MΩ | |
Power frequency withstand Voltage | GB/T13729, AC 3KV 50Hz /1min | |
Impulse voltage | GB/T13729, 5KV, 1.2/50us |
PMC96S selection guide
Model specification: PMC96S-①-②-③-④-⑤ | |
① Model code: | |
1 | 57.7/100V Rated measurement voltage, 5A Rated measurement current. |
2 | 57.7/100V Rated measurement voltage, 1A Rated measurement current. |
3 | 220/380V Rated measurement voltage, 5A Rated measurement current. |
4 | 220/380V Rated measurement voltage, 1A Rated measurement current. |
② Model code: | |
1 | Power supply: 85~264 VAC/45-65Hz, 100~300 VDC. |
③ Model code: | |
0 | Without DI |
2 | 2 Channels DI |
④ Model code: | |
0 | Without relay output |
1 | Optional 1 channel relay output(RL1+, RL1- port) |
2 | Optional 2 channels relay output |
⑤ Model code: | |
ab | ab is a 2 integer, a means AI01 port optional for AI/AO modules, b means AI02portoptional for AI/AO |
0 –none | |
1 - 0-5V DC analog input measure(AI) | |
2 - 4-20mA DC analog input measure(AI) | |
3 - 4-20mA DC analog output(AO) | |
For example: ab = 00, meansnot equipped with AI/AOmodule | |
ab = 21,Means AI01 port is equipped with 0-5V DC analog input measure AI/AOmodule, AI02 port is equipped with 4-20mA DC analog input measure AI/AOmodule |
* Note: PORTS S1, S2 and A1 are multiplexed. If DI is configured, PORT A1 cannot be configured with AI or AO. If port A1 is configured with AI/AO, DI cannot be configured.
For example: Order model: PMC96S-3-1-2-2-20.
Means PMC96S rated measure 220/380V, 5A; working power supply as 85~264 VAC/45-65Hz; Optional with 4channels binary input(DI); 2 channels relay output; 1 channel 4-20mA DC analog input measure(AI02 port).