Item No.: 20601

● PMC96S meter is a multi-functional power monitoring meter, it combines function of collecting data and control, and it can replace many kind of meters, relays, transformers and others components. 

● PMC96S can be installed in different positions of electricity distribution system.

● PMC96S is designed with RS-485 communication interface, which enable itself to be integrated into a variety of power monitoring systems. Data acquisition and remote control can be easily performed through the supporting management software or other industrial configuration software.
3 phase multifunction meter
digital multi function meter
Description
Specification
Ordering Instruction
Product features
  • 22 bit AD is used to realize full power parameter measurement and power metering, with wide dynamic range and high accuracy;
  • Electric parameter out of limit alarm online monitoring, relay related alarm output;
  • Support 2-way DI/DO, power pulse output;
  • Support MODBUS-RTU standard protocol and RS485 communication.


Product Overview

     PMC96S 3 Phase Multifunctional Power Meter adopts pen segment LCD screen, which is simple and beautiful with high contrast; With the high-speed processor as the core, 22 bit AD is used to realize the full power parameter measurement, which has a wide dynamic range and high accuracy. Multiple switch value relays and RS485 communication modules can be optionally configured to meet various functional needs of users: it can easily realize the integration of products with various intelligent power distribution systems with practical, practical and simple functions and easy maintenance. It can be used to monitor and control the status of field equipment, provide measurement support for power application experts, provide data basis for SCADA and smart grid, and provide decision-making basis for efficient and intelligent power management.


Application scenarios

  • Industrial distribution automation system          

  • Energy efficiency management system

  • Substation automation system                            

  • Electrical engineering of intelligent building

  • Power plant auxiliary power system                  

  • High and low voltage switchgear


Electrical Characteristics
Measure type3P3W AC system
3P4W AC system
Samping rate128 points per cycle
Data refresh rate1S
Measure
accuracy
Cureen±0.2%FS
Voltage±0.2%FS
Power0.5S
Frequency±0.001Hz
Active Energy0.5S
Reactive Energy1.0S
DC input(AI)0.5% FS
DC output(AO)0.5% FS
Input voltage
characteristics
Measure Voltage3 *220/380V(Directly input)
3 * 57.7/100V(PT secondary side)
Allowed overload
capability
1.2times / continuous
Input resistance300KΩ/phase
Input current characteristicsMeasure current5A (CT Secondary side)Or 1A (CT Secondaryside)
Allowed overload capability1.2 times/continuous
Input resistance<0.1Ω
Binary inputWorking voltage15 VDC
Input resistance12KΩ
Isolation voltage2KV
Relay OutputNode typeMechanical contact
Node capability220 VAC/5A、30 VDC/5A
4-20mA DC
input measurement
Measure current4-20mA
Allowed overload capability1.2 times / continuous
Input resistance10Ω
Isolation voltage2KV
0-5V DC input measurementMeasure Voltage0-5V
Allowed overload capability1.2times / continuous
Input resistance12.5KΩ
Isolation voltage2KV
4-20mA DC
output
Open-circuit Voltage15VDC
Load capability≤600Ω
Isolation voltage2KV
Power supplyAC85~264 VAC/45-65Hz
DC100~375 VDC
Power consumption< 3W
Mechanical performance
Weight0.5kg
IP Protection LevelMeter Panel IP52,Meter Host IP30
DimensionHost96 X 96 X 72 mm
Host+modules96 X 96 X 120 mm
Working temperatureDisplay screen-20~70℃
Meter-25~70℃
Storage temperatureMeter+display screen-40~85℃
Relative humidity5% - 90%RH, No condensation
EMC
Antistatic discharge interferenceIEC 61000-4-2, Level 4
Anti-fast transient group pulseIEC 61000-4-4, Level 4
Anti-surgeIEC 61000-4-5, Level 3
Resistance to power frequency magnetic fieldIEC 61000-4-8, Level 3
Electrical insulation performance
Insulation resistanceGB/T13729, >50MΩ
Power frequency withstand VoltageGB/T13729, AC 3KV 50Hz /1min
Impulse voltageGB/T13729, 5KV, 1.2/50us


PMC96S selection guide

Model specification: PMC96S-①-②-③-④-⑤
① Model code
157.7/100V Rated measurement voltage, 5A Rated measurement current.
257.7/100V Rated measurement voltage, 1A Rated measurement current.
3220/380V Rated measurement voltage, 5A Rated measurement current.
4220/380V Rated measurement voltage, 1A Rated measurement current.
② Model code
1Power supply85~264 VAC/45-65Hz, 100~300 VDC.
③ Model code
0Without DI
22 Channels DI
④ Model code
0Without relay output
1Optional 1 channel relay output(RL1+, RL1- port)
2Optional 2 channels relay output
⑤ Model code
abab is a 2 integer, a means AI01 port optional for AI/AO modules, b means AI02portoptional for AI/AO
0 –none
1 - 0-5V DC analog input measure(AI)
2 - 4-20mA DC analog input measure(AI)
3 - 4-20mA DC analog output(AO)
For example: ab = 00, meansnot equipped with AI/AOmodule
ab = 21,Means AI01 port is equipped with 0-5V DC analog input measure AI/AOmodule, AI02 port is equipped with 4-20mA DC analog input measure AI/AOmodule


* Note: PORTS S1, S2 and A1 are multiplexed. If DI is configured, PORT A1 cannot be configured with AI or AO. If port A1 is configured with AI/AO, DI cannot be configured.
For example: Order model: PMC96S-3-1-2-2-20.
Means PMC96S rated measure 220/380V, 5A; working power supply as 85~264 VAC/45-65Hz; Optional with 4channels binary input(DI); 2 channels relay output; 1 channel 4-20mA DC analog input measure(AI02 port).