Kingsine Electric Automation Co.,Ltd.
Kingsine Electric Automation Co.,Ltd.
Email Us

KINGSINE K68i Protection Relay Test Set

Item No.: 201040
● The Most Cost-effective, Best field testing convenience in whole of the world.
● 3x35A & 4x300V independent high burden and accuracy output channels.
● Lightweight, <20.5Kg.
● Inbuilt 6.4" True color TFT LCD display, keyboard and rotary encoder, fully control without laptop.
● Advance software testing modules for optional.
● 3-Years guarantee of free repair and life-long maintenance.
● Free software upgrade.
protection relay test
kingsine relay test set
kingsine k68i
Description
Specifications
  • 7 Channels (4x300V & 3x35A) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 20x harmonics.

  • Variable battery simulator, DC 0-300V, 120Watts max.

  • Quick relay testing facility in Manual mode.

  • Switch on to fault test(SOTF).

  • GPS sync end-to-end testing.

  • Online Vector display.

  • Automatic test report creation.

  • Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection.


Basic Functions

  • DC test

  • AC test

  • Distance relay test

  • Harmonic test

  • Frequency test

  • 8 pairs binary inputs

  • 4 pairs binary outputs


Advance Software Functions (Optional for Selections)

  • Differential test

  • State sequence test

  • Time characteristic test

  • Advance distance test

  • Synchronizer test

  • Fault recurrence (fault play back)


Type of Relays Can Be Tested

ItemsANSI® No.
Distance protection relay21
Synchronising or synchronism-check relays25
Undervoltage relays27
Directional Power relays32
Undercurrent or underpower relays37
Negative sequence overcurrent relays46
Overcurrent/ground fault relays50
Inverse time overcurrent/ground fault relays51
Power factor relays55
Overvoltage relays59
Voltage or current balance relays60
Directional overcurrent relays67
Directional ground fault relays67N
DC overcurrent relays76
Phase-angle measuring or out-of-step protection relays78
Automatic reclosing devices79
Frequency relays81
Motor overload protection relays86
Differential protection relays87
Directional voltage relays91
Voltage and power directional relays92
Tripping relays94
Voltage regulating relays
Overimpedance relays, Z>
Underimpedance relays, Z
Time-delay relays


Voltage Outputs
Output Range & Power4×300 V ac (L-N)120 VA max each
3×300 V dc (L-N)120 W max each
Accuracy<0.02%Rd+0.005%Rg Typ.
<0.05%Rd+0.01%Rg Guar.
±10mV @ <5V dc
±0.5% @ ≥5V dc
Voltage RangeRange I: 30V
Range II: 300V
Automatic Range
DC Offset<10mV Typ./ <60mV Guar
Resolution1mV
Distortion<0.015%Typ. / <0.05% Guar.
Current Outputs
Output Range & Power3×35A ac (L-N)450 VA max each
1×105A ac (3L-N)1200 VA max
3×20A dc (L-N)300W max each
Accuracy<0.03%rd+0.02%rg,Typ.
<0.1%rd + 0.05%rg,Guar.
±5mA @ <1A dc
±0.5% @ ≥1A dc
Current RangeRange I: 3A
Range II: 35A
Automatic Range
DC Offset<3mA Typ./ <10mA Guar
Resolution1mA
Distortion<0.025%Typ. / <0.07% Guar.
Frequency & Phase Angle
Frequency RangeDC, 5~1000Hz
Frequency Accuracy±1ppm @ 5~65Hz
±10ppm @ 65~450Hz
±20ppm @ 450~1000Hz
Frequency Resolution0.001 Hz
Phase Range-360°~360°
Phase Accuracy<0.05° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution0.001°
Aux. DC Voltage Source (Battery simulator)
Range0~300V @ 120W max
Accuracy0.5%Rg Guar.
Binary Input
Quantity8pairs
Typewet/dry, up to 300Vdc max input
Time resolution100us
Sampling Rate10KHz
Debounce time0~25ms (Software Controlled)
Time range999.999s
Time errors±1ms @ ≤1s, ±0.1% @ >1s
Galvanic isolationIsolated as 1,2,3,4-8 pairs
Binary Output (Relay Type)
Quantity4pairs
TypePotential free relay contacts, software controlled
Break Capacity ACVmax: 400Vac / Imax:4A / Pmax:1000VA
Break Capacity DCVmax: 300Vdc / Imax:4A / Pmax:300W
Synchronization
Synchronization Mode External GPS (Optional)
Power Supply & Environment
Nominal Input Voltage110V/220/230V ac, appointed, ±15%
Permissible Input Voltage85~264Vac, 125~350VDC, auto-protective
Nominal Frequency50/60Hz
Permissible Frequency45Hz~65Hz
Power Consumption1500 VA max
Connection TypeStandard AC socket 60320
Operating Temperature-10℃~55℃
Storage Temperature-20℃~70℃
Humidity<95%RH, non-condensing
Others
PC ConnectionRJ45 Ethernet, 10/100M
Grounding Terminal4mm banana socket
Weight20.5 Kg
Dimensions(W x D x H)360×450×140(mm)


Products
Products
GET IN TOUCH WITH KINGSINE
Whether you have a question about KINGSINE Electrical Testing Devices or anything else, we're here to help and ready to answer your questions.
E-mail
inquiry@kingsine.com
Call Us
+86-0755-8835-2631
+1 647 707 9669
Headquarter
6C/F4.8 TianAn Cyber Park, Futian, Shenzhen, 518040, China
Contact Us
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. Part of the tracking is necessary to ensure SEO effectiveness,
By using this site, you agree to our use of cookies. Visit our cookie policy to learn more.
Reject Accept