English

Kingsine Electric Automation Co.,Ltd.
Kingsine Electric Automation Co.,Ltd.
Email Us

K3163i Intelligent Protection Relay Test Set

Item No.: 201102

●  All-in-One design, weight < 17.5kg;

●  High Power & Accuracy with 6x35A & 4x310V analog outputs;

●  Complying IEC61850 Sampling Value & GOOSE;

●  The ever-expanding test library templates;

●  Optional advance functions like energy meter and transducer calibration etc.

relay testing in substation
automatic relay tester
Description
Specifications
Advanced
Ordering Instructions
Basic Functions
  • Universal Relay Test Applications.

  • 10 Channels (6x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics.

  • 13 Low-level channels outputs up to 8Vac/10Vdc max.

  • 100/1000Mbit Fiber port for SMV and GOOSE simulations.

  • Variable battery simulator, DC 0-350V, 140Watts max.

  • Transient play back up to 3KHz.

  • Fully function KRT software testing modules.

  • Graphical test modules and templates for testing of various relays.

  • Quick relay testing facility in Manual mode.

  • Shot/Search/Check, Point & Click testing.

  • RIO/XRIO import & export facility.

  • Switch on to fault test(SOTF).

  • Power system model for dynamic testing.

  • Online Vector display.

  • Automatic test results assume.

  • Automatic test report creation.

  • Inbuilt GPS and IRIG-B sync end-to-end testing.

  • Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection.

  • 3-Years guarantee of free repair and life-long maintenance.

  • Lightweight, <18Kg.

  • Free software upgrade.


Advance Feature
  • Complied IEC61850-9-1, IEC61850-9-2, IEC60044-7/8, etc.

  • Transducer calibration (0.02 class).

  • Energy meter calibration (Mechanical & Electronic meters).


Type of Relays Can Be Tested 


Items                                                                                                                                                                   ANSI® No.
IEC61850 numerical IEDs relay & merge unit                                             
Distance protection relay21
Synchronising or synchronism-check relays25
Undervoltage relays27
Directional Power relays32
Undercurrent or underpower relays37
Negative sequence overcurrent relays46
Overcurrent/ground fault relays50
Inverse time overcurrent/ground fault relays51
Power factor relays55
Overvoltage relays59
Voltage or current balance relays60
Directional overcurrent relays67
Directional ground fault relays67N
DC overcurrent relays76
Phase-angle measuring or out-of-step protection relays        78
Automatic reclosing devices79
Frequency relays81
Motor overload protection relays86
Differential protection relays87
Directional voltage relays91
Voltage and power directional relays92
Tripping relays94
Voltage regulating relays
Overimpedance relays, Z>
Underimpedance relays, Z
Time-delay relays


Voltage Outputs
Output Range & Power4×310 V ac (L-N)124 VA max each
3×350 V dc (L-N)140 W max each
Accuracy<0.02%Rd+0.005Rg Typ.
<0.05%Rd+0.01Rg Guar.
±10mV @ <5V dc
±0.5% @ ≥5V dc
Voltage RangeRange I : 30V
Range II : 310V
Automatic Range
DC Offset<20mV Typ./ <100mV Guar
Resolution1mV
Distortion<0.015%Typ. / <0.05% Guar.
Current Outputs
Output Range & Power6×35A ac (L-N)480 VA max each
3×70A ac (2L-N)850 VA max each
1×100A ac (6L-N)1200 VA max
3×20A dc (L-N)300W max each
Accuracy<0.03%Rd+0.02Rg Typ.
<0.1%Rd+0.05Rg Guar.
±5mA @ <1A dc
±0.5% @ ≥1A dc
Current RangeRange I: 3A
Range II: 35A
Automatic Range
DC Offset<3mA Typ./ <10mA Guar
Resolution1mA
Distortion<0.025%Typ. / <0.07% Guar.
Low-Level Output
Quantity13 Channels, 16 pin combination female socket
Voltage Outputs RangeAC 0~8V, DC 0~10V
Current Outputs RangeNominal 2mA, 10mA max transient
Output Power≥0.5VA
Accuracy(0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar.
(0.8~8 Vrms): <0.02% Typ. / <0.05% Guar.
Resolution0.25mV
Distortion (THD%)<0.05% Typ. / <0.1% Guar.
Frequency Range0~3000KHz
DC Offset<0.15mV Typ. / <1.5mV Guar.
Frequency & Phase Angle
Frequency RangeDC~1KHz, 3KHz transient
Frequency Accuracy±0.5ppm
Frequency Resolution0.001 Hz
Phase Range-360°~360°
Phase Accuracy<0.02° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution0.001°
Aux. DC Voltage Source (Battery simulator)
Range0~350V @ 140W max
Accuracy0.5%Rg Guar.
Binary Input
Quantity8pairs
Typewet/dry, measurement
Threshold10~600Vdc or potential free, Programmable
Time resolution10us
Sampling Rate10KHz
Debounce time0~25ms (Software Controlled)
Time rangeInfinite
Time errors±1ms @ ≤1s, ±0.1% @ >1s
Galvanic isolation4 isolated with each 2 pairs
Binary Output (Relay Type)
Quantity4pairs
TypePotential free relay contacts, software controlled
Break Capacity ACVmax: 400Vac / Imax:8A / Pmax:2500VA
Break Capacity DCVmax: 300Vdc / Imax:5A / Pmax:150W
Binary Output (Semiconductor Type)
Quantity4pairs
Type:Open-collector, Combination type female
Break Capacity DC5~15Vdc / 5mA, 10mA max
AC not permit
Response time:100us
Synchronization
Synchronization Mode GPS, SMA type antenna connector
IRIG-B (Optical fiber, FT3 type)
Power supply & Environment
Nominal Input Voltage100~240Vac
Permissible Input Voltage85~260Vac, 125~350VDC
Nominal Frequency50/60Hz
Permissible Frequency45Hz~65Hz
Power Consumption1500 VA max
Connection TypeStandard AC socket 60320
Operating Temperature-10℃~55℃
Storage Temperature-20℃~70℃
Humidity<95%RH, non-condensing
Others
PC ConnectionRJ45 Ethernet, 10/100M
Grounding Terminal4mm banana socket
Weight17.5 Kg
Dimensions(W x D x H)468×375×164(mm)


(Optional Modules)

IEC61850 Functions:

  • Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8)

  • Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function.

  • Up to 36 sampling value channels can be mapped.


IEC61850 Fiber & GOOSE Ethernet Ports (Optional Function)
Fiber Ports                                    2 x 100Base-FX Full Duplex, LC type
(Optional to 10/100Mbit, Ethernet RJ45 type)
Fiber Type62.5/125um (Multiple optical fiber, Orange Red)
Wavelength1310nm
Transmit Distance                                                                                  >1Km
IndicatorSpd Green(light): Valid connection
Link/Act Yellow(Blinking): Data exchanging
NoteHardware is ready, to be active


Transducer Calibration Function:

DC Measurement Input  (Hardware is ready, to be active)
Voltage InputRange0~±10V dc
Max Input±11V dc
Accuracy<0.2% rg Typ. <0.5% rg Guar.
Input Impedance1M ohm
Current InputRange0~±1mA / 1~±20mA, auto range
Max Input600mA
Accuracy<0.2% rg Typ. <0.5% rg Guar.
Input Impedance15 ohm


Energy Meter Calibration Function:

Energy Meter Calibration (Hardware is ready, to be active)
Sensor UsageMechanical meters / Electronic meters
Sensor OutputHigh lever: >4.5V, Low level: <0.2V
Pulse Input1 pulse input port, 5Vdc high level valid only.
Pulse Range500KHz pulse input Max.
Pulse Output1 Transistor output, Open-collector, 5Vdc/5mA


ModelCurrent OutputsVoltage OutputsOptional
K3166i6×35A @ 450VA max
3×70A @ 850VA max
7×310V @ 90VA max
  • IEC61850 SV

  • IEC61850 GOOSE

  • Energy meter cal.

  • Transducer cal.

K3163i6×35A @ 450VA max
3×70A @ 850VA max
4×310V @ 124VA max
K3130i3×35A @ 450VA max4×310V @ 124VA max