English

Kingsine Electric Automation Co.,Ltd.
Kingsine Electric Automation Co.,Ltd.
Email Us

KF932 IEC61850 Relay Tester

Item No.: 203006
● The most light and powerful handheld digital relay tester for IEC61850 testing;
● Applied to digital protection relay, Measure & control device, IEC61850 Complying IEDs, Merge Unit and substation control system testing and detection;
● Touch screen and keypad, to meet different using habits.
● 4400mAh large capacity lithium battery, continuous work for more than 10 hours.
● Small size, easy to portable.
relay testing device
relay tester
relay testing machine
relay tester kit
Description
Specifications
Advance Feature

Basic Functions

  • KF932 IEC61850 Relay Tester is developed based on the intelligent substation related standards to analyze the SV, GOOSE, IRIG-B and IEEE1588 message, calculate the magnitude, phase and frequency of voltage and current, and real-time monitor of GOOSE virtual terminal.

  • Receiving closed-loop testing of smart devices via SV, GOOSE message sending, subscription and publication of GOOSE messages.

  • Phase detection function is achieved by analyzing and calculating different control blocks; Binary input and output of the hard contact can be completed on the intelligent operation box transmission delay and SOE on the accuracy of the measurement.

  • SV and GOOSE exception statistics analysis and synchronization function to achieve the integration of the unit discrete, lost frame and absolute delay measurement.

  • With small size, touch screen operation of the convenience and powerful measurement and analysis and testing capabilities, greatly to meet the intelligent substation operation, maintenance and debugging of the protection, monitoring and control devices, IEC61850 complying IEDs, the merger unit and the station control system Detection and commissioning requirements.

Power Supply
BatteryLarge capacity lithium battery
Power AdapterInput:AC100~240V, 50/60Hz, 0.7A
Output:DC15V, 1.66A
Power Consumption
Power consumption≦6W
Working power supplyContinuous work for more than 10 hours
Optical Ethernet Communication Port
Model100Base-FX (100M Full duplex optical fiber network)
Port TypeLC
Wavelength1310nm
Transmission distance≧1km
ApplicationIEC61588 Times and other network messages
Optical Serial Port Communication Interface
Port number2 pcs
Port TypeST
Wavelength62.5/125μmMultimode fiber, Wavelength850nm
Transmission distance≧1km
ApplicationReceive/Send IEC60044-7/8(FT3), IRIG-B Timing signal transceiver
Analog Input Communication Interface
Port number1 pair
Port TypeRubber terminal
Hard contact input/output communication interface
Port number2 pairs
Port TypeAviation socket to rubber terminal
TF Card Slot Interface
Port number1 pc
ApplicationTF card for importing the whole station configuration file, recording documents, storing/exporting test reports and upgrading software.
Analog input communication interface
Port number1 pair
Time Signal
IRIG-BTime accuracy<1us typ
IEC 61588Time accuracy<1us typ
Mechanical Parameters
Display screen4.3' touch LCD screen
Size176×100×58 mm
Weight≦0.75kg
Temperature Range
Altitude≤5000m
Ambient temperatureNormal operating temperature:-10~55℃
Storage and transportation:-25~85℃
Relative humidity5%~95%
Atmospheric pressure60~106KPa


No.Analysis ItemAnalysis content
SMV Measurement and analysisInterceptionAutomatically intercepts SV messages from 3 optical ports and 1 optical interface
Effective valueReal-time display channel of amplitude, phase and frequency
OscillographyReal-time display of waveform
Sequence componentReal-time display the positive sequence V1, negative sequence V2, zero positive sequence V0 of magnitude and phase
PowerReal-time display of ABC phase and three-phase active, reactive power, apparent power and power factor
Vector graphThe magnitude and phase relationship of the three-phase voltage and current are displayed in vector form
HarmonicReal-time display 0 ~ 19 harmonics, and show the harmonic content in the form of histograms
Message parameterReal-time display of the current message parameters, the original message and parsed message
Abnormal
message
The number of abnormal message
Discrete
Value
The number of messages in each discrete
GOOSE analytic and analysisInterceptionAutomatically intercepting GOOSE messages from 3 optical ports
Virtual terminalReal-time display of the status of the virtual terminal, support a variety of display. Automatically record the reset time of the virtual terminal.
MessageReal-time display of the current message value and the original message value.
Abnormal messageThe number of abnormal message
OthersRecorderRecord and analyze off-line messages
Measurement of flow and optical powerReal-time statistics of network traffic size and received optical power
PCAP message analysisOffline analysis of messages stored in PCAP format
Polarity testTest the polarity of the transformer
MeasurementManual testThrough the output of SV messages, GOOSE message simulation and sub subscription together with the binary input and output of hard contact to protect, monitor and control of the IED device test.
State sequencerBy outputting multiple consecutive states, for user-defined tests.For each individual state, the magnitude, phase, and frequency of the voltage and current can be set. Setting up the status of GOOSE virtual terminals to meet various test requirements.
IEDMeasuring the transfer delay and SOE time accuracy between the GOOSE and the hard contact.
Superimposed harmonic2~19 harmonics are superimposed on the output fundamental voltage and current to realize the test of IED devices such as protection, measurement and control.


GET IN TOUCH WITH KINGSINE
Whether you have a question about KINGSINE Electrical Testing Devices or anything else, we're here to help and ready to answer your questions.
E-mail
inquiry@kingsine.com
Call Us
+86-0755-8835-2631